BASIC PRODUCT DATA
Duct Wrap may be used to insulate most heating, ventilating and air conditioning ductwork at temperatures from 35°F to 250°F (1.7°C to 121°C) for faced duct wrap, and from 35°F to 350°F (1.7°C to 177°C) for unfaced duct wrap. The FSK and white PSK facing have a 0.02 perm rating. The gray PSK has a 0.09 perm rating.
COMPLIANCES
Duct wrap products meet the requirements of the following current specifications and standards:
- Material Specifications ASTM C 1290, ASTM C 553. The FSK facing meets the requirements of ASTM C 1136, Type II.
- Fire Safety Standards NFPA 90A, NFPA 90B
- Model Building Code ICC
- GREENGUARD® Children & Schools